Home

Call Us Now: 905-676-9888 (Dealers Only)

Welcome to cctvdirect.ca,

Call Us Now: 905-676-9888 (Dealers Only)

Welcome to cctvdirect.ca,

Call Us Now: 905-676-9888 (Dealers Only)

Welcome to cctvdirect.ca,

More Views

PRO1500RT

Quick Overview

• Designed for PCs, telephone and security systems, and data communications
• Protects equipment from harmful AC power surges and spikes
• Built-in boost and buck AVR (Automatic Voltage Regulation) function compensates for broader range of AC voltage situations like surges and spikes, saving internal battery   power for blackouts and extending the life of the batteries
• Includes Minuteman SentryPlus power management and diagnostic software to provide added control and allow unattended PC shutdown (for use on individual PCs or    multiple workstations or networks      
• Integrated USB port for software communications (USB cable included)
• Independent Battery Bypass allows the UPS to provide voltage regulation with surge or spike protection even when batteries are weak or dead.
• 8 outlets (6 outlets with battery backup / surge protection and 2 outlets with surge protection only).

Availability: Out of stock

Line-Interactive UPS with 8 Outlets TAA Compliant

VA Rating 1500VA
Max Output Power 1050Watts
Output Receptacles (6) NEMA 5-15R Battery & surge (2) NEMA 5-15R Surge only
Input Connection 10 ft. Power cord with NEMA 5-15P
Voltage 120VAC
Voltage Regulation 50/60Hz ±5Hz, auto-sensing
AC Leakage Current <1.0mA at full rated non-linear load
Input Protection Resettable circuit breaker
Voltage 120VAC
Voltage Regulation Nominal ±5% until low battery warning
Frequency 50/60Hz, ±0.5Hz (unless synchronized to utility)
Wave Form Simulated sine wave
Typical Transfer Time 6-10 ms (max 10ms)
Overload Capacity 110% for 10 seconds, 120% shutdown immediately
Protection Over-current, short-circuit protected, and latching shutdown
Estimated Runtimes - Full/Half Load 5 min. / 17 min.
Hot Swappable Battery Yes
Internal Battery Module BM0044
DC Leakage Current <30uA (±10uA) with no AC applied and the unit in the o position
Battery Type Sealed, non-spillable, maintenance-free, valve-regulated lead acid
Surge Energy rating 1140 joules
Surge Current Capacity AC Normal, On Battery, Overload, Weak/Bad/Disconnected Battery, Internal Fault
Surge Response Time 0-ns (instantaneous) normal mode; <5ns common mode
Temperature 0º to +40ºC / +32º to +104ºF
Humidity 0 to 95% non condensing
Elevation 0 to +3,000 m / 0 to +10,000 ft
Weight Lbs/Kgs: 43.0 / 19.5
Dimensions (H x W x D) 3.5" x 17.3" x 15.7"