Line-Interactive UPS with 8 Outlets TAA Compliant
VA Rating | 1500VA |
---|---|
Max Output Power | 1050Watts |
Output Receptacles | (6) NEMA 5-15R Battery & surge (2) NEMA 5-15R Surge only |
Input Connection | 10 ft. Power cord with NEMA 5-15P |
Voltage | 120VAC |
Voltage Regulation | 50/60Hz ±5Hz, auto-sensing |
AC Leakage Current | <1.0mA at full rated non-linear load |
Input Protection | Resettable circuit breaker |
Voltage | 120VAC |
Voltage Regulation | Nominal ±5% until low battery warning |
Frequency | 50/60Hz, ±0.5Hz (unless synchronized to utility) |
Wave Form | Simulated sine wave |
Typical Transfer Time | 6-10 ms (max 10ms) |
Overload Capacity | 110% for 10 seconds, 120% shutdown immediately |
Protection | Over-current, short-circuit protected, and latching shutdown |
Estimated Runtimes - Full/Half Load | 5 min. / 17 min. |
Hot Swappable Battery | Yes |
Internal Battery Module | BM0044 |
DC Leakage Current | <30uA (±10uA) with no AC applied and the unit in the o position |
Battery Type | Sealed, non-spillable, maintenance-free, valve-regulated lead acid |
Surge Energy rating | 1140 joules |
Surge Current Capacity | AC Normal, On Battery, Overload, Weak/Bad/Disconnected Battery, Internal Fault |
Surge Response Time | 0-ns (instantaneous) normal mode; <5ns common mode |
Temperature | 0º to +40ºC / +32º to +104ºF |
Humidity | 0 to 95% non condensing |
Elevation | 0 to +3,000 m / 0 to +10,000 ft |
Weight | Lbs/Kgs: 43.0 / 19.5 |
Dimensions (H x W x D) | 3.5" x 17.3" x 15.7" |